How it works
Where the heat would go
Illustrative energy flows
Where energy would go
Redwood Materials is our preferred storage supplier. We intend to use Redwood Energy second-life EV battery storage, subject to procurement, engineering, and agreement. No partnership or capacity is confirmed. Redwood also offers new batteries; the pack mix would need agreement. Storage could buffer short power peaks and bridge brief interruptions (ride-through). Controls would schedule charging and discharge (dispatch). Operating apart from the grid (islanding) would depend on inverters, protection, controls, and system testing. We guarantee neither black start nor uptime. No storage size or carbon savings is proposed. The storage flows are relative units, not MW or MWh. The fuel-cell scenario does not model a linear generator.
The widths show illustrative proportions at one design point. They are not engineering results. No biogas supply is assumed.
Heat would serve glasshouses, fungi rooms, buildings, homes, and the wastewater plant. Full-load closed-loop dry coolers would send surplus heat to air. Bubblers would move air only.
Early years: nearby users could take about a quarter of the computer heat. Dry coolers would send the rest to air. The share used would grow only as heat customers connected.
No creek withdrawal, discharge, or heating is planned.
View flows as a table
| From | To | Relative units |
|---|---|---|
| Natural gas | Fuel cells | 86 |
| Grid | Grid import | 6 |
| Grid import | Redwood Energy BESS | 2 |
| Grid import | AI data halls | 4 |
| Redwood Energy BESS | AI data halls | 2 |
| Fuel cells | AI data halls | 43 |
| Fuel cells | Fuel-cell heat | 21 |
| Fuel cells | Conversion losses | 22 |
| AI data halls | Heat pumps & thermal storage | 12 |
| AI data halls | Dry coolers (air) | 37 |
| Heat pumps & thermal storage | Glasshouses | 4 |
| Heat pumps & thermal storage | Utility heat network | 3 |
| Heat pumps & thermal storage | Buildings | 2 |
| Heat pumps & thermal storage | Domestic hot water | 2 |
| Heat pumps & thermal storage | Fungi rooms | 1 |
| Fuel-cell heat | Wastewater plant heating | 3 |
| Fuel-cell heat | Utility heat network | 4 |
| Fuel-cell heat | Glasshouses | 2 |
| Fuel-cell heat | Dry coolers (air) | 12 |
01
Fuel-cell heat and computer heat
Fuel-cell heat comes from fuel energy left after generating electricity. Exhaust heat could be hot enough for district heating and digesters.
Computer heat would be captured by liquid cooling at about 35–50 °C (assumed until the equipment is specified). Glasshouses and fungi rooms could use it. Heat pumps could raise its temperature for homes.
Computer heat comes from electricity; fuel-cell heat comes from the remaining fuel energy. We would account for them separately to avoid counting the same energy twice.
02
Temperatures and seasons
| Use | Typical supply temperature | Seasonality |
|---|---|---|
| Glasshouses | 35–50 °C | Highest in winter nights |
| Fungi rooms | 18–25 °C ambient | Steady year-round |
| Domestic hot water | 55–65 °C (heat pump uplift) | Steady year-round |
| District space heating | 45–70 °C | Winter peak, summer near zero |
| Digester heating | 35–40 °C (mesophilic) | Year-round, higher in winter |
Computers would produce heat year-round, while demand would peak in winter. Heat storage would smooth daily changes, and heat pumps would raise temperatures where needed. Full-load closed-loop dry coolers would send surplus heat to air in summer, with none going to the creek.
Illustrative estimate
Heat and energy calculator
Nearly all electricity used by computers becomes heat. This estimates annual quantities from your assumptions. Nothing has been measured.
Share of fuel energy converted to electricity.
Share of fuel energy recoverable as heat.
Theoretical recoverable computer heat
30.3
GWh of low-grade heat per year
- Facility electricity
- 43.5 GWh/yr
- Supply
- Fuel cells (proposed base)
- Gas input (fuel)
- 87.0 GWh/yr
- Fuel-cell heat (separate, hotter)
- 21.8 GWh/yr
- Conversion losses
- 21.8 GWh/yr
- Gas volume
- 297k MMBtu/yr
- Direct CO₂ only
- 15.8k t/yr
- Assumptions & limits
- Recoverable GPU heat = IT load × average load factor × recovery × 8,760 h ÷ 1,000. Treats IT electricity as equal to heat output.
- Facility electricity = IT load × average load factor × PUE × 8,760 h. Gas input = facility electricity ÷ electrical efficiency.
- Computer heat comes from electricity; fuel-cell heat comes from the remaining fuel energy. We keep these streams separate because their temperatures differ, and never sum them into one total.
- CO₂ uses the EPA factor of 53.06 kg CO₂ per MMBtu of natural gas fuel. Upstream methane leakage, grid emissions and lifecycle impacts are excluded and would raise the figure.
- These theoretical upper limits omit seasonal demand, distribution losses, heat-pump electricity, and downtime. They are not forecasts or commitments.
- 4.8 MW of computing (IT load) is the proposed pilot and 9.6 MW the proposed first node. *16.8, 24 and 42 MW are conditional later scenarios; 42 MW IT is a study ceiling with no approval or binding commitment. Gas capacity and legal thresholds require utility and counsel verification.